SGE400

Specification & Dimension:
Generator Model SGE400
Output rating (kVA)
50 Hz
380V
Prime
400
Standby
425
60 Hz
440V
Prime
415
Standby
455
Rated current (A)
50 Hz
Prime
608.8
Standby
669.7
60 Hz
Prime
544.6
Standby
597.1
Rated frequency / rated speed
50 Hz
1500 RPM
60 Hz
1800 RPM
No. of poles
4 poles
Phase and wire
3-Phase 4-wire
Power factor
0.8 (lagging)
Voltage regulation
Within +/- 1.5 %
Excitation
Brushless, Rotating Exciter (with AVR)
Insulation
Class ‘F’
Engine Model
DC13072A
Type of combustion chamber
Direct Injection
Air intake system
Turbo Charged
Output rating (kW)
1500 RPM (50 Hz)
365
1800 RPM (60 Hz)
410
Rated speed (50/60Hz, rpm)
1500 / 1800
Bore (mm) x stroke (mm)
130 x 160
Piston displacement (L)
12.7
No. of cylinders
6 in line
Governor type
EMS – EUI
Fuel consumption (L/hr) at 100% load
50 Hz
73.9
60 Hz
76.9
Lubricating oil capacity (L)
30
Coolant capacity (L)
22
Fuel tank capacity (L)
Open Type
750
Sound Proof Type
1000
Starting motor (v-kW)
24 – 5.5
Charging generator (V-A)
28 – 100
Battery capacity (V-Ah)
12 – 150 x 2
Starting system
Electric Starting Motor – Air to Air Charge Air Cooler
Cooling system
Radiator with fan
Lubricating system
Forced lubrication with trochoid pump
Soundproof Dimension (approx.)
L
mm
5320
W
mm
1600
H
mm
2100
Approx dry weight
kg
4500
Open Type Dimension (approx.)
L
mm
3650
W
mm
1180
H
mm
2150
Approx dry weight
kg
3500

 

Note
Prime output rating
Supplies electric power continuously at variable load.
No limitation to the annual hours of operation and can supply 10% overload power for 1 hour in 12 hours
Conforms with SAE J816B continuous, DIN 6270, BS 6270, BS 5514 or 649 continuous & ISO 3046/I continuous power.
Standby output rating

Supplies electricity during normal utility power failure at variable load.
No overload is permitted on this rating.
Conforms with SAE J816B intermittent, DIN 6270, BS 5514 or 649 one hour & ISO 3046 / 1 fuel stop power.

Engine output represents at ISO 3046, standard conditions
Air Temperature
25C
Relative humidity
30%
Barometric pressure
750 mmHg

 

Note: This specification is subject to change without notice due to our continuous product improvement.

​