YTG75TLV

Full Range:

Single Leaflet:

Generator Model YTG75tlV
Output rating (kVA)
50 Hz
380V
Prime
60.0
Standby
66.0
60 Hz
440V
Prime
65.0
Standby
70.0
Rated current (A)
50 Hz
Prime
91.3
Standby
100.4
60 Hz
Prime
85.3
Standby
91.8
Rated frequency / rated speed
50 Hz
1500 RPM
60 Hz
1800 RPM
No. of poles
4 poles
Phase and wire
3-Phase 4-wire
Power factor
0.8 (lagging)
Voltage regulation
Within +/- 1.5 %
Excitation
Brushless, Rotating Exciter (with AVR)
Insulation
Class ‘F’
Engine Model
4tnV106t
Type of combustion chamber
Direct Injection
Air intake system
Turbocharged
Output rating (kW)
1500 RPM (50 Hz)
50.9
1800 RPM (60 Hz)
60.9
Rated speed (50/60Hz, rpm)
1500 / 1800
Bore (mm) x stroke (mm)
106 x 125
Piston displacement (cm3)
4412
No. of cylinders
4
Fuel
Diesel Fuel ASTM 2D
Fuel consumption (L/hr) at 100% load
50 Hz
11.7
60 Hz
12.6
Lubricating oil capacity (L)
14
Coolant capacity (L)
6
Fuel tank capacity (L)
sound proof
155
open skid
170
Starting motor (v-kW)
12 – 3.0
Charging generator (V-A)
12 – 60
Battery capacity (V-Ah)
12 – 65 x 1
Starting system
Electric Starting Motor
Cooling system
Radiator with fan
Lubricating system
Forced lubrication with trochoid pump
Soundproof Dimension (approx.)
L
mm
2400
W
mm
920
H
mm
1450
Approx dry weight
kg
1362
Sound Level dBA from 1 meter / 7 meter
dBA
78 / 68
Open Type Dimension (approx.)
L
mm
1780
W
mm
700
H
mm
1250
Approx dry weight
kg
1045

 

Note
Prime output rating
Supplies electric power continuously at variable load.
No limitation to the annual hours of operation and can supply 10% overload power for 1 hour in 12 hours
Conforms with SAE J816B continuous, DIN 6270, BS 6270, BS 5514 or 649 continuous & ISO 3046/I continuous power.
Standby output rating

Supplies electricity during normal utility power failure at variable load.
No overload is permitted on this rating.
Conforms with SAE J816B intermittent, DIN 6270, BS 5514 or 649 one hour & ISO 3046 / 1 fuel stop power.

Engine output represents at ISO 3046, standard conditions
Air Temperature
25C
Relative humidity
30%
Barometric pressure
750 mmHg

Note: This specification is subject to change without notice due to our continuous product improvement.

​